AZ-50. Commercial refrigeration. ASHRAE safety class A1, temperature glide about 0.1 °F. Gauge pressure at sea level.

ChargeCheck for iPhone is coming to the App Store.

°FLiquid / bubble (psig)Vapor / dew (psig)
-405.45.4
-358.18.1
-3011.011.0
-2514.114.1
-2017.617.6
-1521.421.4
-1025.525.5
-530.030.0
034.834.8
540.140.0
1045.745.7
1551.851.7
2058.358.2
2565.365.2
3072.772.7
3580.780.7
4089.389.2
4598.398.3
50108.0107.9
55118.3118.2
60129.2129.1
65140.7140.6
70153.0152.9
75165.9165.8
80179.6179.5
85194.1193.9
90209.3209.1
95225.4225.2
100242.3242.1
105260.1259.8
110278.8278.6
115298.5298.2
120319.2318.9
125340.9340.6
130363.8363.5
135387.8387.5
140413.0412.7
145439.5439.3
150467.5467.3

Negative values are inches of vacuum territory shown as negative psig. Use the dew column for superheat and the bubble column for subcooling. Try the superheat calculator.

Other refrigerants: R-410A · R-454B · R-32 · R-22 · R-134a · R-404A · R-407C · R-1234yf