Superheat & subcooling calculator
Gauge pressures, line temperatures and the manufacturer's target in; superheat, subcooling and "within / outside entered target range" out. 9 refrigerants, dew point for suction and bubble point for liquid.
ChargeCheck for iPhone is coming to the App Store.
How it works
Superheat = suction line temperature minus suction saturation temperature (dew point). Subcooling = liquid saturation temperature (bubble point) minus liquid line temperature.
The calculator does not work out a target and never says a charge is correct. You enter the target from the manufacturer: target superheat from the charging chart for a fixed orifice / piston, target subcooling from the nameplate or installation guide for a TXV / EEV. The controlling value is compared to that target ± tolerance (default ±5 °F superheat, ±3 °F subcooling). No check is made below 55 °F outdoor, on ductless / inverter systems (charged by weight), or on commercial and automotive refrigerants; superheat under 3 °F always shows "Check readings".
PT data: CoolProp 8.0 (NIST reference equations) and the Chemours R-454B table, checked against Arkema charts within 0.1 psi. See the R-410A PT chart.