ChargeCheck

R-22 PT chart

HCFC-22, Freon 22. Legacy AC (service only). ASHRAE safety class A1. Gauge pressure at sea level.

ChargeCheck for iPhone is coming to the App Store.

°Fpsig
-400.6
-352.6
-304.9
-257.4
-2010.2
-1513.2
-1016.5
-520.1
024.0
528.3
1032.8
1537.8
2043.1
2548.8
3055.0
3561.5
4068.6
4576.1
5084.1
5592.6
60101.6
65111.2
70121.4
75132.2
80143.6
85155.7
90168.4
95181.8
100195.9
105210.8
110226.4
115242.8
120260.0
125278.0
130296.9
135316.7
140337.4
145359.0
150381.7

Negative values are inches of vacuum territory shown as negative psig. Use the dew column for superheat and the bubble column for subcooling. Try the superheat calculator.

Other refrigerants: R-410A · R-454B · R-32 · R-134a · R-404A · R-407C · R-507A · R-1234yf