ChargeCheck

R-404A PT chart

HP62, FX-70. Commercial refrigeration. ASHRAE safety class A1, temperature glide about 0.9 °F. Gauge pressure at sea level.

ChargeCheck for iPhone is coming to the App Store.

°FLiquid / bubble (psig)Vapor / dew (psig)
-404.94.3
-357.56.8
-3010.39.6
-2513.412.7
-2016.816.0
-1520.519.7
-1024.623.6
-528.927.9
033.732.6
538.837.7
1044.343.1
1550.249.0
2056.655.3
2563.462.1
3070.769.3
3578.677.1
4086.985.4
4595.894.2
50105.3103.6
55115.3113.6
60126.0124.2
65137.3135.5
70149.3147.4
75162.0160.1
80175.4173.4
85189.5187.5
90204.5202.4
95220.2218.1
100236.8234.7
105254.2252.1
110272.6270.4
115291.8289.7
120312.1309.9
125333.4331.2
130355.7353.6
135379.1377.1
140403.7401.7
145429.6427.7
150456.8455.0

Negative values are inches of vacuum territory shown as negative psig. Use the dew column for superheat and the bubble column for subcooling. Try the superheat calculator.

Other refrigerants: R-410A · R-454B · R-32 · R-22 · R-134a · R-407C · R-507A · R-1234yf